Certificates and Declaration
Conformity to standard #1 | UL 61010-1 Guide PICQ File E257746 |
---|---|
Conformity to standard #2 | CSA-C22.2 No. 61010-1 |
Conformity to standard #3 | IEC 61557-12 |
Conformity to standard #4 | ISO 14025 |
Proposition 65 California | WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov |
Certificates and Declaration - Safety
Safety standards | IEC/EN 61010-1 UL 61010-1 CAN/CSA C22.2 No. 61010-1 |
---|---|
UL file number | E257746 |
Classification
UNSPSC | 83101808 |
---|---|
ETIM Class | EC002301 |
IGCC | 6042 |
Environmental Sustainability
PEP Filename | SOCO-00090-V01.01-EN.pdf |
---|---|
Climate change - Total - Cradle to Grave [kg COâ‚‚ eq.] | 33 |
Climate change - Total - Cradle to Gate [kg COâ‚‚ eq.] | 7 |
ETIM - Electrical characteristics
Sampling frequency [Hz] | 10000 |
---|---|
Number of voltage measurement inputs | 4 |
Voltage type (supply voltage) | DC |
Supply voltage DC [V] | 0..24 |
Measuring range for frequency [Hz] | 45..65 |
Supporting protocol for IEC 61850 Ethernet | No |
Supporting protocol for OPC UA PubSub | No |
Supporting protocol for PROFIBUS | No |
Supporting protocol for Modbus | Yes |
Supporting protocol for PROFINET IO | No |
Supporting protocol for other bus systems | No |
With audit logging (audit log) | No |
With firmware signature | Yes |
With logging of security events (security event log) | No |
With Role Based Access Control (RBAC) | No |
Web server with HTTPS transfer protocol | No |
ETIM - Mechanical characteristics
Width [mm] | 18 |
---|---|
Height [mm] | 90 |
Depth [mm] | 65 |
ETIM - Technical features
Ampere meter | No |
---|---|
Blind power meter | Yes |
With rotational speed meter | No |
Frequency meter | Yes |
Pulse counter | No |
Voltmeter | Yes |
Effective power measurement device | No |
Display | None |
Remote display | No |
General Product Characteristics
Device type | Voltage measurement module |
---|
Logistics
GTIN/EAN | 3596032783778 |
---|---|
Customs number | 9030337000 |
Price unit | PC |
Weight of the packing unit [kg] | 0.09 |
Length of the packing unit [m] | 0.12 |
Width of the packing unit [m] | 0.081 |
Depth of the packing unit [m] | 0.034 |
Product Details
Effective date | 2014-01-22 |
---|---|
Offer Life Cycle Code | 40 |
Country of origin | FR |
Standards
Conformity to standards |
|
---|
Technical Characteristics
Application | Metering |
---|---|
Model | U-10 |
Rated voltage | 87..520 VAC (L-L) |
Type | AC voltage acquisition module |
Technical Characteristics - Electrical
Max voltage (Phase/neutral) | 50-300 VAC (Ph/N) |
---|
Technical Characteristics - Environmental
Maximum operating altitude | 6560 feet / 2000 m |
---|---|
Operating temperature | +14 to +158 °F / -10 to +70 °C |
Storage temperature | -13 to +158 °F / -25 to +70 °C |
Technical Characteristics - Measurement
Accuracy class | Class 0.2 |
---|---|
Degree of Pollution | 2 |
Frequency rating | 45 … 65 Hz |
Full measurement range | 50-300 VAC (Ph/N) - 87-520 VAC (Ph/Ph) - CAT III |
General measurements | Multi-measurement: U12, U23, U31, V1, V2, V3, f |
Voltage measurement type | AC |